Accuracy class
This article needs additional citations for verification. (April 2024) |
Accuracy classes are defined and used in IEC and ANSI standards. Classes are denoted by either a letter or percentage. For example, Class B is a temperature accuracy from IEC-751 that requires accuracy of ± 0.15 degrees Celsius. Class 0.5 is an ANSI C12.20 accuracy class for electric meters with absolute accuracy better than ± 0.5% of the nominal full scale reading.[1]
Typically, a class specifies accuracy at a number of points, with the absolute accuracy at lower values being better than the nominal "percentage of full scale" accuracy.
Accuracy classes such as IEC's 0.15s are a 'special' high accuracy class.[2]
Calculation for accuracy of class 1 meter: 1600 impulse/KWh and considering, P.F= 1 and LOAD = 100w Revolution time, Rt = (3600×Kh×1)/Load(w) [Kh = 1000/(impulse/Kwh=1600)] Rt = (3600×0.625×1)/100 Rt = 22.5sec [Standard]
%of error = (Ft-Rt)/Rt
The positive or negative result indicates whether the meter is fast or slow. If the result is positive, then the meter is fast, while negative means the meter is slow.
References
[edit]- ^ "Accuracy class - Knowledge - Dalian Huayi Electric Power Electric Appliances Co., Ltd". www.hyee-current-transformer.com. Retrieved 2024-04-01.
- ^ "accuracy classの意味・使い方・読み方 | Weblio英和辞書". ejje.weblio.jp. Retrieved 2024-04-01.