Description Faulty Sakno silicone foam firestop installation in a Calgary wastewater treatment plant in the 1980's. This is a hole in a fire-resistance rated concrete wall, above a fire door frame. The outside temperature was ca. -40°C (-40 F). The inside was heated. A steady temperature is needed for the foam to "snap", solidify and expand properly, as it evolves hydrogen gas. Every now and then someone opened the outside door, the temperature would plummet and the foam's consistency was affected, as can be seen by the tears and uneven bubble distribution and incomplete phase change. To achieve its rating, as per its certification listing, the foam also requires ceramic fibre boards (furnace insulation) to permanently cover both sides of the foam, a common deficiency, exposed by whistleblower Gerald W. Brown. This is image 1 of 2. The other one is right here: http://commons.wikimedia.org/wiki/Image:Silicone_foam_sakno2.jpg .
Date
Source Own work
Author Achim Hering

Licensing

Public domain This work has been released into the public domain by its author, I, Achim Hering. This applies worldwide.
In some countries this may not be legally possible; if so:
I, Achim Hering grants anyone the right to use this work for any purpose, without any conditions, unless such conditions are required by law.

Captions

Add a one-line explanation of what this file represents

Items portrayed in this file

depicts

10 July 2007

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current02:47, 11 July 2007Thumbnail for version as of 02:47, 11 July 20074,591 × 3,157 (1.17 MB)Achim Hering{{Information |Description=Faulty Sakno silicone foam firestop installation in a Calgary wastewater treatment plant in the 1980's. This is a hole in a fire-resistance rated concrete wall, above a [[fire d

The following page uses this file:

Global file usage

The following other wikis use this file:

Metadata